24 AWG, bare copper wire insulated with thermoplastic. Three layer core construction jacketed with PVDF fluoropolymer (plenum), or PVC (riser).
Standards
Flame Rating
Applications
Berk-Tek's Multi-Pair Type III Power Sum UTP cables are intended for voice applications.
Features
Ideally suited for backbone, cross-connect and pre-connectorized assemblies
Benefits
400 PR (CMR)
400 PR (CMP)
Mutual Capacitance, nF/100 m nom.
6.6
DC Resistance, Ohms/100 m max.
9.4
Conductor diameter—in. (mm)
0.02 (0.51)
Cable diameter—in. (mm)
1.652 (41.94)
1.545 (39.23)
Nominal cable weight lb/k ft. (kg/km)
1499 (2219)
FrequencyMHz
Insertion LossdB/100 m max.
SRLdB min.
PS-NEXTdB min.
1
2.6
12
41.3
4
5.9
32.3
10
10.9
26.3
16
15.3
23.3
Pair 1
White/Blue
Blue/White
Pair 13
Black/Green
Green/Black
Pair 2
White/Orange
Orange/White
Pair 14
Black/Brown
Brown/Black
Pair 3
White/Green
Green/White
Pair 15
Black/Gray
Gray/Black
Pair 4
White/Brown
Brown/White
Pair 16
Yellow/Blue
Blue/Yellow
Pair 5
White/Gray
Gray/White
Pair 17
Yellow/Orange
Orange/Yellow
Pair 6
Red/Blue
Blue/Red
Pair 18
Yellow/Green
Green/Yellow
Pair 7
Red/Orange
Orange/Red
Pair 19
Yellow/Brown
Brown/Yellow
Pair 8
Red/Green
Green/Red
Pair 20
Yellow/Gray
Gray/Yellow
Pair 9
Red/Brown
Brown/Red
Pair 21
Violet/Blue
Blue/Violet
Pair 10
Red/Gray
Gray/Red
Pair 22
Violet/Orange
Orange/Violet
Pair 11
Black/Blue
Blue/Black
Pair 23
Violet/Green
Green/Violet
Pair 12
Black/Orange
Orange/Black
Pair 24
Violet/Brown
Brown/Violet
Pair 25
Violet/Gray
Gray/Violet
Application note: If installing as 6 4-pr. connections, use sequential pairs (1-4, 5-8, etc.) to ensure standard performance
Installation
0°C to +50°C
Operation
-10°C to +60°C