FIREX MC cables are rugged armored cables suitable for installation in a wide range of commercial and industrial applications where excellent mechanical and physical properties are required.
Applications
FIREX MC is suitable and allowed by the NEC for use in the following applications:
- for power, lighting and control circuits and as a branch circuits and power feeders in industrial, commercial, institutional and residential installations up to 600 V.
- fished or embedded in plaster and concrete.
- direct buried or used as an aerial cable when fixed to a messenger support cable.
- used in concealed or exposed applications.
- installed in cable trays and other raceways.
- in Class I and II, Division 2 as well Class III, Division 1 and 2 hazardous locations.
- under raised floors of information technology rooms.
- where exposed to harsh chemicals and vapors
Identification of Conductors
Colored insulation with/without stripe per Method #1-E2 in ICEA S-73-532.
Bending Radius
Fixed position: 7 x cable overall diameter
During pulling: 12 x cable overall diameter
Specifications
- Meets UL 44, XHHW-2 600V conductors
- Meets UL 1569 requirements for Type MC, Metal Clad cables
- Designated Type MC per NEC Article 330
Product features
- Cables are UL listed as Type MC, 600 V
- UL listed insulated conductors
- Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEEE 1202 and CSA FT4
- Cables exhibit a -25°C cold bend rating with suitable precautions
- Temperature rating of 90°C dry and wet
- 130°C emergency rating and 250°C short circuit rating
- Excellent mechanical and physical properties
- Sunlight and oil resistant jacket
- LEAD FREE
- Suitable for direct burial and use in cable tray and embedment in concrete
- Can be installed in hazardous locations designated Class I or Class II Division 2, NEC Articles 501.10(B), 502.10(B) and Class III Division 1 and 2, NEC Article 503.10 (A) and (B)
|