FIREX MC cables are rugged armored cables suitable for installation in a wide range of commercial and industrial applications where excellent mechanical and physical properties are required.
Applications
FIREX MC is suitable and allowed by the NEC for use in the following applications:
Identification of Conductors
Power and control: sizes #14 AWG to #10 AWG: Method #1-E2 per ICEA S-73-532 sizes #8 AWG to 500 kcmil: Method #4 per ICEA S-73-532
Bending Radius Fixed position: 7 x cable overall diameter During pulling: 12 x cable overall diameter
Specifications
Product features
Part Number
Cond.Size
Insulation Thickness
GroundWire Size
Nominal Diameterover Armor
Jacket Thickness
Nominal Diameterover Jacket
Approximate NetCable Weight
Ampacity
AWG/kcmil
mils
mm
AWG
inches
lb/kft
kg/km
amps (1)
660702
8(7w)
45
1.14
10(7w)
0.783
19.89
50
1.27
0.889
22.58
462
688
55
660703
6(7w)
0.879
22.33
0.985
25.01
637
947
75
651216
4(7w)
1.005
25.53
1.113
28.27
893
1329
95
649293
2(7w)
1.148
29.17
1.256
31.90
1298
1932
130
662360
1(19w)
1.40
1.260
32.00
1.368
34.74
1547
2302
150
660704
1/0(19w)
1.379
35.02
1.487
37.77
1901
2829
170
645481
2/0(19w)
1.483
37.67
1.591
40.42
2293
3412
195
662125
3/0(19w)
1.586
40.29
60
1.52
1.714
43.53
2825
4204
225
649301
4/0(19w)
1.720
43.68
1.847
46.92
3474
5170
260
660407
250(37w)
65
1.65
2.042
51.86
2.171
55.15
4073
6062
290
660673
350(37w)
3(7w)
2.293
58.23
1.92
2.454
62.33
5817
8657
350
640508
500(37w)
2.603
66.12
2.765
70.22
7890
11742
430
(1) Ampacities are in accordance with Table 310.16 of the NEC for conductors in raceway or direct buried at 30°C ambient temperature and 90°Cconductor temperature, where the 4th conductor is the neutral of a balanced 3 phase system. If the 4th conductor is to be used as a currentcarrying conductor, then a derating factor of 80% is to be applied to the ampacity of all 4 conductors, as per Article 310.15(B)(2)(a) of the NEC.For correction factors for different ambient temperatures and ampacities at different conductor temperatures, see Table 310.16 of the NEC.