Login Get Registered Catalog Browser Contact Us
Electrical Cable, Data Cable, and Specialty Cables

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

FIREX® MV 5 kV Unshielded Cables

Send link to this page print Your Nexans contact on this page
Aluminum Interlocked Armored Power Cables UL Type MV-90, 90°C rated 2.4 kV* or 5 kV* non-shielded, XLPE insulation, aluminum interlocked armor, PVC jacket
Standards
National  ICEA S-96-659; UL 1072
Description

Applications

FIREX MV is suitable and allowed by the NEC for use in the following applications:

  • for power feeders in industrial, commercial, institutional and residential installations up to 5000 volts. (2400 volts per NEC)
  • fished or embedded in plaster and concrete.
  • direct buried or used as an aerial cable when fixed to a messenger support cable.
  • used in concealed or exposed applications.
  • installed in cable trays and other raceways.
  • in Class I and II, Division 2 as well as Class III, Division 1 and 2 hazardous locations.
  • where exposed to harsh chemicals and vapors.
     

Construction

Conductor
Bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8.

Conductor shield
Extruded thermosetting semi-conducting layer.

Insulation
XLPE as per UL 1072 and ICEA S-96-659.

Assembly
Insulated conductors are cabled with a bare copper grounding conductor(s) and interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape of synthetic material assembles the core in an essentially round configuration.

Armor
Interlocking aluminum tape armor applied directly over the core.

Jacket
Overall polyvinyl chloride jacket, 90°C temperature rating; low acid gas emission; limited flame spread and excellent corrosion resistance.

Conductor Identification
Number coded.

Bending Radius
Fixed position: 7 x cable overall diameter
During pulling: 12 x cable overall diameter


 TOP
FIREX® MV 5 kV Cables
UL Type MV-90, 90°C rated

2.4 kV* or 5 kV* Unshielded, 3 Conductors with Bare Ground
Insulation Thickness:  90 mils / 2.29 mm

Part 
Number

Conductor
Size

Ground
Wire Size

Nominal
Diameter
over Armor

Jacket 
Thickness

Nominal 
Diameter
over Jacket

Approximate
Cable Weight

Ampacity

AWG/kcmil

AWG

inches

mm

mils

mm

inches

mm

lb/kft

kg/km

amps (1,2)

amps (3)

------

8 (7w)

8 (7w)

1.055

26.80

50

1.27

1.165

29.59

605

900

59

85

------

6 (7w)

6 (7w)

1.130

28.70

50

1.27

1.240

31.50

785

1168

79

105

------

4 (7w)

6 (7w)

1.235

31.67

50

1.27

1.345

34.16

990

1473

105

135

------

2 (7w)

6 (7w)

1.360

34.54

60

1.52

1.470

37.34

1295

1927

140

180

------

1 (19w)

6 (7w)

1.465

37.21

60

1.52

1.575

40.01

1515

2255

160

200

------

1/0 (19w)

4 (7w)

1.555

39.50

60

1.52

1.685

42.80

1855

2761

185

230

------

2/0 (19w)

4 (7w) 

1.650

41.91

60

1.52

1.780

45.21

2175

3237

215

260

------

3/0 (19w)

4 (7w) 

1.785

45.34

60

1.52

1.915

48.64

2700

4018

250

295

650754

4/0 (19w)

3 (7w)

1.905

48.39

60

1.52

2.030

51.56

3230

4807

285

335

------

250 (37w)

3 (7w)

2.015

51.18

60

1.52

2.145

54.48

3655

5439

320

365

650747

350 (37w)

2 (7w)

2.235

56.77

75

1.91

2.365

60.07

4795

7136

395

440

650663

500 (37w)

1 (19w)

2.510

63.75

75

1.91

2.675

67.95

6535

9725

485

530

641464

750 (61w)

1/0 (19w)

2.905

73.79

85

2.16

3.070

77.98

9245

13758

615

650

------

1000 (61w)

1/0 (19w)

3.335

84.71

85

2.16

3.410

86.61

11850

17635

705

730

(1)  Ampacities for cable in air in accordance with Table 310.71 of NEC, conductor temperature of 90°C and ambient air temperature of 40°C.
(2) Ampacity for cable in ventilated tray in accordance to Article 392.13(A)(2) and Table 310.71 of NEC.
(3) Ampacity for one cable direct buried in accordance with Table 310.83 with 90°C conductor temperature, R.H.O.. 90, 100% load factor, 
20°C earth temperature.


 TOP
Selling delivery information

OPTIONS

 

The following constructions can be provided on special orders:

  • Aluminum conductors
  • Steel interlock armor
  • Extra ground wires
  • Special color or number coding
  • Specially colored jackets
  • Other constructions and combinations (some manufacturing restrictions apply)

* The NEC and UL 1072 limit unshielded cable to circuits operating at a maximum of 2400 volts phase to phase. ICEA S-96-659 rates unshielded cable with the same insulation thickness to a maximum operating voltage of 5000 volts phase to phase.


Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map