ENERGEX® AC HCF

Send link to this page print Your Nexans contact on this page
Aluminum Armored Health Care Facilities UL Type AC, Copper Conductors, 600 V, 90°C dry rated - LEAD FREE
Standards
National  UL 1581; UL 4; UL 83
Description

Applications
ENERGEX® AC cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction. They may be used in patient areas of hospitals, out-patient centers and medical and dental offices. They are not permitted where hazardous anesthetizing is performed. They may also be used in applications which require AC cable with a redundant ground in accordance with NEC Article 250.118(8). They are suitable for installation in accordance with applicable requirements of NEC Articles 320 and 517. These cables may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300.22(C) ONLY.

Nexans AC HCF cable is LEAD FREE and RoHS compliant.

Construction

Conductor:
Solid conductors are soft bare annealed copper to ASTM B3. Stranded conductors are soft bare annealed copper to ASTM B3 and ASTM B8.

Insulation:
PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test.

Bond Wire:
Longitudinal aluminum bond wire (16 AWG) in contact with armor.

Ground Wire:
Bare copper, sized in accordance with NEC and UL, with green THHN insulation.

Assembly:
Conductors are individually paper wrapped and cabled with a marker tape/core protection tape combination which assembles the core in an essentially round configuration.

Armor:
Interlocking aluminum tape armor applied directly over the core.

Marker Tape Print:
ALUMINUM ARMORED CABLE NOT FOR USE ON DC CIRCUITS / CAUTION NOT TO BE USED WITH SET SCREW CONNECTOR / FOR CT USE LEAD FREE (MFG DATE)

Specifications

* Meets UL 4: Armored Cable
* Meets UL 83: Thermoplastic-Insulated Wires and Cables
* Meets UL 1581: Reference Standard for Electrical Wires, Cables, and Flexible Cords
* Designated Type AC per NEC Article 320
* Meets UL 2556: Wire and Cable Test Methods
* Meets NEC: 250.94, 250.118(8), 300.22(C), 320, 517.13 and 645


 TOP
Characteristics
Construction characteristics
Conductor material Copper  
Lead free Yes  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ENERGEX® AC HCF

Part
Number

Number of
Conductors

Conductor
Size

Ground
Size

Circuit 
Conductor
Color Code 

Nominal Diameter 
over Armor

Approximate Net
Cable Weight

Ampacity

250 ft coil

1000 ft reel

AWG

AWG

inches

mm

lb/kft

kg/km

amps

671560

672170

2

12 (1)

12 (1)

white/black

0.487

12.37

132

197

20

672188

672196

3

12 (1)

12 (1)

white/black/red

0.521

13.23

161

240

20

673426

673434

4

12 (1)

12 (1)

white/black/red/blue

0.547

13.89

196

291

20*

673715

673723

2

10 (1)

10 (1)

white/black

0.503

12.78

181

269

30

673731

673749

3

10 (1)

10 (1)

white/black/red

0.537

13.64

225

335

30

673756

673764

4

10 (1)

10 (1)

white/black/red/blue

0.585

14.86

271

403

30*

---

676460

2

12 (19)

12 (19)

white/black

0.487

12.37

135

201

20

676478

676486

3

12 (19)

12 (19)

white/black/red

0.521

13.23

165

246

20

Bend Radius:  7 x overall diameter
Notes:  Dimensions and weights shown are nominal values.  They are subject to standard 
industry tolerances.  Ampacity in accordance with Table 310.16 of NEC for copper 
conductors at 30°C ambient temperatures.
*Ampacity assuming 4th (white) conductor is a grounded phase conductor (neutral).


 TOP
Selling delivery information

Product Features

  • Cables are UL listed as Type AC, 600 V
  • UL listed insulated conductors
  • UL listed for use in cable trays per NEC 320.10(2)
  • Temperature rating of 90ºC dry
  • Excellent mechanical and physical properties
  • Lightweight aluminum armor
  • LEAD FREE


Options

The following constructions can be provided on special orders: