ENERGEX® 8000 Mobile Home Feeder USE-2 / RHH / RHW-2 Aluminum

Send link to this page print Your Nexans contact on this page
USE-2 / RHH / RHW-2 XLPE Insulated, ACM Aluminum Conductors, 600 Volts, 90ºC Dry and Wet - LEAD FREE
Standards
National  UL 44; UL 854
Description

Application

Nexans ENERGEX®  Mobile Home Feeder is a twisted assembly of USE-2 / RHH / RHW-2 insulated aluminum conductor material (ACM), AA-8000 series alloy conductors.  The cable is used as a service cable to feed mobile homes in parks and permanent locations.  ENERGEX® 8000 Mobile Home Feeders are designed to be directly buried.  The cable is rated at 600 volts for use in wet and dry locations in accordance with NEC 2008 and NEC 2011 Article 550.33.

Nexans Mobile Home Feeder cables are LEAD FREE.

        

Construction

Conductor
Compact stranded AA-8000 series aluminum alloy per ASTM B800 and B801

Insulation:
Solid color-coded sunlight resistant cross-linked polyethylene (XLPE)

Assembly:
Black and red conductors are cabled with the white neutral conductor and green equipment grounding conductor

 

Specifications

  • Meets UL 854: Service Entrance Cables
  • Meets UL 44: Thermoset - Insulated Wires and Cables

Surface Print Legend (example)

  • NEXANS-C 4/0 AWG COMPACT AA-8000-AL USE-2 OR RHH OR RHW-2 600V SUN RES LEAD FREE (UL) (MFG. DATE)

 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
Lead free Yes  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ENERGEX® 8000 USE-2 / RHH / RHW-2 Mobile Home Feeder Aluminum

Cable
Construction
(Ph 1 + Ph 2 + N + G)

Insulation Thickness
Phase Conductors

Insulation Thickness
Neutral Conductor

Insulation Thickness 
Grounding Conductor

Cable
Diameter
inches

Approximate Net
Cable Weight

Ampacity

amps

mils

mm

mils

mm

mils

mm

lb/mft

kg/km

2 + 2 + 4 + 6

60

1.52

60

1.52

60

1.52

0.94

301

448

100

4/0 + 4/0 + 2/0 + 4

80

2.03

80

2.03

60

1.52

1.53

794

1182

200

• Where stated, "nominal" and "approximate" values are provided for information purposes 
only and are subject to standard manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 Table 310.15(B)(6) or NEC 2011 Table 310.15(B)(7) 
and are based on 90º C conductor temperature, 20º C ambient earth temperature, earth thermal 
resistivity Rho=90, cables buried 36" deep, only the phase conductors carrying current, and 100% load factor.


Package Quantities and Part Numbers

Cable Construction
(Ph 1 + Ph 2 + N + G)

Package Quantity / Part Number

500 ft reel

1000 ft reel

Long Lengths
Cutting Reels

2 + 2 + 4 + 6

680061

680062

680060

4/0 + 4/0 + 2/0 + 4

680075

680076

680073


 TOP
Selling delivery information

Product Features

  • Cables are UL listed as Service Entrance Cable
  • Solid color insulation
  • Temperature rating of 90°C dry and wet
  • Sunlight Resistant
  • LEAD FREE
  • Bare conductors are heat treated after stranding for maximum flexibility