ENERGEX® 8000 USE-2 / RHH / RHW-2 Aluminum
Description
XLPE Insulated Cable, 600 Volts, 90ºC Dry or Wet - LEAD FREE - NEC ART 310 and ART 338, ACM Aluminum Conductors
Description
Standards
National : ICEA S-95-658; UL 44; UL 854Description
Applications
Nexans ENERGEX® RHH/RHW-2/USE-2 conductors may be installed in raceways and conduits or directly buried. They are 90°C, 600 volts per NEC Articles 310 and 338.
Type USE-2 conductors are suitable as service entrance conductors which can be installed directly buried in accordance with the NEC.
When used as type RHH, the cables are suitable for installation in dry locations.
As type RHW-2 and USE-2, cables are suitable for installation in both wet and dry locations.
Nexans RHH/RHW-2/USE-2 conductors are Lead Free.
Construction
Conductor: compact stranded AA-8000 series aluminum alloy (ACM) per ASTM B800 and B801.
Insulation: Heat, sunlight, moisture and abrasion resistant cross-linked polyethylene (XLPE) insulation per UL 854 and UL 44. Black only.
Specifications
- Meets UL 44: (RHH, RHW-2) Thermoset Insulated Wires and Cables
- Meets UL 854 (USE-2) Service Entrance Cables
- Federal Specification A-A-59544
- ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- National Electrical Code – NFPA 70
- Conductors 1/0 AWG and larger (4 AWG and larger in green) are rated CT use
Surface Print Legend
NEXANS-C 1/0 AWG COMPACT AA-8000-AL USE-2 OR RHH OR RHW-2 600V FOR CT USE SUN RES (UL) LEAD FREE (MFG. DATE)
Product features
- Cables are UL listed as Type USE-2
- Temperature rating of 90°C dry and wet
- Suitable for direct burial
- Sunlight resistant
- Lead Free
- Bare conductors are heat treated after stranding for maximum flexibility
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Aluminium |
| Lead free | Yes |
| Electrical characteristics | |
| Maximum operating voltage | 600V |
| Usage characteristics | |
| Maximum operating temperature | 90°C |
Docs and info
ENERGEX® 8000 USE-2 / RHH / RHW-2 600 V Aluminum
|
Conductor Size |
Nominal Insulation Thickness |
Nominal Diameter |
Approximate Net Cable Weight |
Ampacity* |
|||||
|
AWG/kcmil |
mils |
mm |
inches |
mm |
lb/kft |
kg/km |
60 ºC |
75 ºC |
90 ºC |
|
6 (7) |
60 |
1.52 |
0.29 |
7.4 |
47 |
70 |
40 |
50 |
55 |
|
4 (7) |
60 |
1.52 |
0.33 |
8.4 |
66 |
98 |
55 |
65 |
75 |
|
2 (7) |
60 |
1.52 |
0.39 |
9.9 |
96 |
143 |
75 |
90 |
100 |
|
1 (18) |
80 |
2.03 |
0.46 |
11.7 |
127 |
189 |
85 |
100 |
115 |
|
1/0 (18) |
80 |
2.03 |
0.50 |
12.7 |
152 |
226 |
100 |
120 |
135 |
|
2/0 (18) |
80 |
2.03 |
0.54 |
13.7 |
182 |
271 |
115 |
135 |
150 |
|
3/0 (18) |
80 |
2.03 |
0.59 |
15.0 |
222 |
330 |
130 |
155 |
175 |
|
4/0 (18) |
80 |
2.03 |
0.64 |
16.3 |
271 |
403 |
150 |
180 |
205 |
|
250 (35) |
95 |
2.41 |
0.71 |
18.0 |
328 |
488 |
170 |
205 |
230 |
|
300 (35) |
95 |
2.41 |
0.76 |
19.3 |
385 |
573 |
195 |
230 |
260 |
|
350 (35) |
95 |
2.41 |
0.81 |
20.6 |
435 |
647 |
210 |
250 |
280 |
|
400 (35) |
95 |
2.41 |
0.85 |
21.6 |
494 |
735 |
225 |
270 |
305 |
|
500 (35) |
95 |
2.41 |
0.93 |
23.6 |
600 |
893 |
260 |
310 |
350 |
|
600 (58) |
110 |
2.79 |
1.07 |
27.2 |
721 |
1073 |
285 |
340 |
385 |
|
700 (58) |
110 |
2.79 |
1.11 |
28.2 |
828 |
1232 |
315 |
375 |
425 |
|
750 (58) |
110 |
2.79 |
1.13 |
28.7 |
899 |
1338 |
320 |
385 |
435 |
|
1000 (58) |
110 |
2.79 |
1.28 |
32.5 |
1141 |
1698 |
375 |
445 |
500 |
|
*60ºC - When terminated to equipment for circuits rated 100 amperes or less or marked for |
|||||||||
Selling information
Product Features
- Cables are UL listed as Service Entrance Cable
- Solid color insulation
- Temperature rating of 90°C dry and wet
- Sunlight Resistant
- LEAD FREE
- Bare conductors are heat treated after stranding for maximum flexibility