ENERGEX® 8000 Aluminum SER
Description
Service Entrance Type SE, Style R, XLPE Insulated ACM Aluminum Conductors. 600 Volts, 90°C Dry or Wet - LEAD FREE
Description
Standards
National : UL 854Description
Application
Nexans ENERGEX® 8000 SER is type SE, Style R cable, used as an above ground service entrance cable, a panel feeder and in branch circuits. The cable is rated at 600 volts and 90ºC for use in wet and dry locations in accordance with NEC 2008 and NEC 2011 Article 338.
Nexans SER cables are LEAD FREE and RoHS compliant.
Construction
Conductor:
Compact stranded AA-8000 series aluminum alloy (ACM) per ASTM B801 or B836. #8 AWG is solid AA-8000 series aluminum alloy per ASTM B800 and B801 (8 AWG is solid).
Insulation:
Color coded cross-linked polyethylene (XLPE).
Assembly:
Insulated conductors are cabled with the bare ground wire. A flame retardant fiberglass reinforced binder tape assembles the core in a circular configuration.
Jacket:
Sunlight resistant, LEAD FREE, flame retardant, gray polyvinyl chloride (PVC) material.
Conductor Identification:
Color coded: Black, White and Red
Specifications
Meets UL 854: Service Entrance Cables
Surface Print Legend (example)
- NEXANS-C ENERGEX 8000 TYPE SE - STYLE: R 600V XHHW AA-8000-AL 3/C 4/0 AWG + 1C 2/0 AWG (UL) E-49786 SUN RES LEAD FREE (MFG. DATE)
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Aluminium |
| Lead free | Yes |
| Electrical characteristics | |
| Maximum operating voltage | 600V |
| Usage characteristics | |
| Maximum operating temperature | 90°C |
Docs and info
ENERGEX 8000 SER - 3 Insulated Conductors with Bare Ground
|
Insulated |
Insulation Thickness |
Bare |
Jacket Thickness |
Nominal Diameter |
Approximate Net |
Ampacity* |
|||||||
|
mils |
mm |
mils |
mm |
inches |
mm |
lb/kft |
kg/km |
Dwelling |
60°C |
75°C |
90°C |
||
|
8 (1) |
45 |
1.14 |
8 (1) |
30 |
0.76 |
0.56 |
14.2 |
130 |
193 |
- |
30 |
40 |
45 |
|
6 (7) |
45 |
1.14 |
6 (7) |
30 |
0.76 |
0.67 |
17.0 |
185 |
275 |
- |
40 |
50 |
55 |
|
4 (7) |
45 |
1.14 |
6 (7) |
30 |
0.76 |
0.74 |
18.8 |
243 |
362 |
- |
55 |
65 |
75 |
|
2 (7) |
45 |
1.14 |
4 (7) |
30 |
0.76 |
0.88 |
22.4 |
350 |
521 |
100 |
75 |
90 |
100 |
|
1 (18) |
55 |
1.40 |
2 (7) |
30 |
0.76 |
0.97 |
24.6 |
451 |
671 |
110 |
85 |
100 |
115 |
|
1/0 (18) |
55 |
1.40 |
2 (7) |
30 |
0.76 |
1.05 |
26.7 |
553 |
823 |
125 |
100 |
120 |
135 |
|
2/0 (18) |
55 |
1.40 |
1 (18) |
30 |
0.76 |
1.14 |
29.0 |
696 |
1036 |
150 |
115 |
135 |
150 |
|
3/0 (18) |
55 |
1.40 |
1/0 (18) |
30 |
0.76 |
1.22 |
31.0 |
780 |
1161 |
175 |
130 |
155 |
175 |
|
4/0 (18) |
55 |
1.40 |
2/0 (18) |
30 |
0.76 |
1.32 |
33.5 |
956 |
1423 |
200 |
150 |
180 |
205 |
|
*60°C – When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. |
|||||||||||||
Related documents
Selling information
Product Features
- Cables are UL listed as Type SE, Style R
- Temperature rating of 90°C dry and wet
- Sunlight Resistant
- Moisture Resistant
- LEAD FREE and RoHS compliant
- Bare conductors are heat treated after stranding for maximum flexibility