ENERGEX® NM-B Copper

Send link to this page print Your Nexans contact on this page
PVC/Nylon Insulated Cable, Copper Conductors, 600 Volts, 90ºC Dry Rated - LEAD FREE
Standards
National  UL 719; UL 83
Description

Application

Nexans non-metallic sheathed ENERGEX® NM-B cable is used in normally dry installations in residential wiring, as branch circuits for outlets, lighting and other residential loads.  Its applications are outlined in NEC 2008 and NEC 2011 Article 334. NM-B is rated at 600 volts and although it is rated at a conductor temperature of 90ºC dry , its ampacity is limited to 60ºC according to the NEC 2008 and NEC 2011.  It may be fished through masonry or tile walls, where not exposed or subject to excessive moisture or dampness.

Nexans NM-B cables are LEAD FREE and RoHS compliant.

  

Construction

Conductor
Solid 14 to 10 AWG annealed soft bare copper per ASTM B3. 
Stranded 8 AWG and larger annealed soft bare copper per ASTM B3 and B8.

Insulation:
Color coded polyvinyl chloride (PVC) compound with a nylon covering meeting the required thickness of Type THHN.  Conductor insulation is rated 90ºC.

Ground:
Soft, bare copper solid per ASTM B3 and stranded per ASTM B3 and B8

Sheath:
30 mil color coded PVC sheath rated 90°C is applied over the completed assembly:
White  14 AWG
Yellow  12 AWG
Orange  10 AWG
Black  8 to 2 AWG

 

Specifications

  • Nexans ENERGEX®  NM-B meets or exceeds all applicable ASTM specifications.
  • UL 83: Thermoplastic Insulated Wires and Cables
  • UL 719: Non-Metallic Cables
  • Federal Specification A-A-59544 and requirements of the NEC.
  • Voltage rating - 600 volts.

 

Surface Print Legend (example)


NEXANS-C ENERGEX 2C-14 AWG TYPE NM-B 600V W/GRD (UL) LEAD FREE MM/DD/YY/ MADE IN U.S.A. 


 TOP
Characteristics
Construction characteristics
Conductor material Copper  
Lead free Yes  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ENERGEX® NM-B Copper

Conductor
Size
AWG

# of
Conductors

PVC Insulation
Thickness

Ground
Wire Size
AWG

Nylon 
Thickness

Nominal Cable
Dimensions

Approximate Net
Cable Weight

Ampacity
Amps

mils

mm

inch

mm

mils

mm

lbs/kft

kg/km

  Two Conductor

14 (1)

2

15

0.38

14 (1)

4

0.10

0.16 x 0.36

4.0 x 9.1

57

85

15

12 (1)

2

15

0.38

12 (1)

4

0.10

0.17 x 0.40

4.3 x 10.2

82

122

20

10 (1)

2

20

0.51

10 (1)

4

0.10

0.21 x 0.49

5.3 x 12.4

124

185

30

8 (7)

2

30

0.76

10 (1)

5

0.13

0.27 x .059

6.9 x 15.0

186

277

40

6 (7)

2

30

0.76

10 (1)

5

0.13

0.32 x 0.68

8.1 x 17.3

255

379

55

  Three Conductor

14 (1)

3

15

0.38

14 (1)

4

0.10

0.31

7.9

74

110

15

12 (1)

3

15

0.38

12 (1)

4

0.10

0.34

8.6

107

159

20

10 (1)

3

20

0.51

10 (1)

4

0.10

0.43

10.9

163

243

30

8 (7)

3

30

0.76

10 (1)

5

0.13

0.56

14.2

254

378

40

6 (7)

3

30

0.76

10 (1)

5

0.13

0.63

16.0

357

531

55

4 (7)

3

40

1.02

8 (7)

6

0.15

0.85

21.6

593

882

70

2 (7)

3

40

1.02

6 (7)

6

0.15

0.98

24.9

856

1274

95

  Four Conductor

14 (1)

2/2¹

15

0.38

14 (1)

4

0.10

0.35

8.9

91

135

15

14 (1)

15

0.38

14 (1)

4

0.10

0.35

8.9

91

135

15

12 (1)

2/2¹

15

0.38

12 (1)

4

0.10

0.38

9.7

132

196

20

12 (1)

15

0.38

12 (1)

4

0.10

0.38

9.7

132

196

20

Notes:

• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject 
to standard manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15 and 334.80, which are based on NEC 2008
Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature
and 60°C rated conductors.
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see 
NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 
20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient 
temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and 
NEC 2011 Article 240.4(E) through (G).

¹  Insulation color code for 2 / 2 conductor cable is Black, White, Red, and White with Red stripe.  Cable ampacity 
is based on the White and White with Red Stripe conductors being connected as the neutrals for the system.
². Insulation color code for 4 conductor cable is Black, White, Red and Blue.  Cable ampacity is based on the 
4th conductor being connected as the neutral conductor of a balanced 3 phase system.


 TOP
Selling delivery information

Product Features

  • Slick proprietary sheathing material designed for ease of installation
  • Color coded sheaths designed for quick cable identification
  • LEAD FREE and RoHS compliant
  • 14 AWG 2c and 12 AWG 2c available with two neutral conductors

 

Packaging

  • 14, 12 & 10 AWG; 2, 3 and 4 conductor - 250 ft coil and 1000 ft reel
  • 8 AWG and larger 2 and 3 conductor - 125 ft coil, 500 and 1000 ft reel