Nexans ENERGEX® THHN/THWN-2/MTW* is a general purpose wiring product for use in power, lighting and control circuits. It can be used in conduit, ducts and trays for service feeders and branch circuits in industrial and commercial installations. When used in accordance with the 2008 or 2011 NEC, THHN/THWN-2 is suitable for use in wet and dry locations, at conductor temperatures not exceeding 90ºC or for use in oil or coolants at conductor temperatures not exceeding 75ºC. THHN/THWN-2 is gasoline and oil resistant II. When used as Machine Tool Wire (MTW) it is rated at 90ºC in dry locations and 60ºC in wet locations or when exposed to oil or coolants.
Nexans THHN/THWN-2/MTW wire is LEAD FREE and RoHS compliant.
Conductor: Solid bare, annealed copper per ASTM B3. Stranded bare annealed copper per ASTM B3 and ASTM B8. 14, 12, 10 and 8 AWG and ASTM B8 for sizes 6 AWG and larger.
Insulation: Color coded polyvinyl chloride (PVC), heat, moisture and flame retardant compound per UL 83 and UL 1063.
Covering: A tough abrasion resistant polyamide (Nylon) covering.
NEXANS-C 500 kcmil (253mm2) TYPE MTW OR THHN OR THWN-2 GRII SR FOR CT USE VW-1 600V (UL) LEAD FREE (MFG. DATE)
ConductorSizeAWG/kcmil
PVC InsulationThickness
NylonThickness
Nominal Diameter
Approximate NetCable Weight
Ampacity
Amps
mils
mm
inches
lbs/kft
kg/km
60ºC
75ºC
90ºC
14 (1)
15
0.38
4
0.10
0.11
2.80
22.3
12 (1)
0.12
3.10
23
34.2
20
10 (1)
0.51
0.15
3.80
37
53.6
30
14 (19)
16
23.8
12 (19)
0.13
24
35.7
10 (19)
0.17
4.30
39
58.0
8 (19)
0.76
5
0.22
5.60
63
93.7
40
50
55
6 (19)
0.26
6.60
98
145
65
75
4 (19)
1.01
6
0.33
8.40
157
234
70
85
95
3 (19)
0.36
9.10
193
287
100
110
2 (19)
0.39
9.90
240
357
115
130
1 (19)
1.27
7
0.18
0.43
10.9
300
446
150
1/0 (19)
0.47
12.0
376
560
125
170
2/0 (19)
0.52
13.2
467
695
175
195
3/0 (19)
0.57
14.5
581
864
165
200
225
4/0 (19)
0.64
16.0
724
1077
230
260
250 (37)
60
1.52
8
0.20
0.69
17.4
855
1272
215
255
290
300 (37)
19.3
1022
1521
285
320
350 (37)
0.79
20.1
1191
1772
310
350
400 (37)
0.85
21.6
1345
2001
280
335
380
500 (37)
0.94
23.9
1668
2482
430
600 (61)
1.78
9
0.23
1.10
27.9
1994
2967
355
420
475
750 (61)
1.16
29.5
2465
3668
400
535
60ºC - When terminated to equipment for circuits rated 100 amperes or less or marked for conductor sizes 14 through 1 AWG. For MTW in wet locations or when exposed to oil or coolant.75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG. THWN-2 when exposed to oil or coolant.90°C - THHN dry locations. THWN-2 wet or dry locations. For ampacity derating purposes.Available colors: Black, White, Red, Blue, Green, Yellow, Brown, Orange, Purple, Gray, Pink.Notes:• Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing tolerances.• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient temperature.• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC 2008 and NEC 2011 Article 240.4(E) through (G).
* Only stranded cables are MTW listed per UL 1063.