Description
Standards
National : FAA L-824 Type CDescription
Applications
Nexans FAA L-824 Type C airport series runway lighting cable is designed for use in between the constant current source and the isolating transformers in the series lighting circuits for runways, taxiways, navigational aids, and obstruction lighting (such as LED, Xenon, and Incandescent light fixtures). It is suitable for direct burial installations, pulled into metallic or non-metallic conduit (where not exceeding the pulling tension and sidewall bearing pressure limits). These XLPE insulated cables are rugged, have excellent abrasion and crush resistance, and are resistant to the chemicals in de-icing fluids. Manufactured in the U.S., and being lead free and RoHS compliant make this cable an attractive solution.
Construction
The single conductor 5 kV rated cable is used underground, direct buried and in ducts to feed series lighting circuits and navignational aids.
Conductor: Bare, annealed compressed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8.
Conductor shield: No conductor shield for this construction
Insulation: Black cross-linked polyethylene
Specifications
- Meets FAA L-824 Type C
Product Features
- Made in the U.S.A.
- ARRA (American Recovery and Reinvestment Act of 2009) compliant
- Suitable for installation in metallic and non-metallic conduits
- Suitable for direct burial underground
- Temperature rating of 90°C dry and wet
- LEAD FREE and RoHS complaint
Termination and Splicing
For unshielded airport lighting cables, standard techniques and accessories may be used (with adequate insulation build-up).
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Bare annealed copper |
| Conductor shape | Compressed |
| Armour type | Unarmoured |
| Insulation | XLPE (chemical) |
| Colour | Black |
| Lead free | Yes |
| Electrical characteristics | |
| Maximum operating voltage | 5000V |
| Usage characteristics | |
| RoHS conform | Yes |
Docs and info
FAA L-824 Type C 5000 Volts Non-Shielded
|
Part Number |
Package |
Conductor |
Insulation |
Nominal |
Approximate Net |
|||
|
ft |
AWG |
mils |
mm |
inches |
mm |
lb/kft |
kg/km |
|
|
660615 |
5,000 |
8 (19w) |
110 |
2.79 |
0.366 |
9.30 |
87 |
130 |
|
660616 |
5,000 |
6 (19w) |
110 |
2.79 |
0.404 |
10.26 |
123 |
183 |
|
611491 |
5,000 |
8 (7w) |
110 |
2.79 |
0.369 |
9.37 |
89 |
132 |
|
670231 |
10,000 |
8 (7w) |
110 |
2.79 |
0.369 |
9.37 |
89 |
132 |
|
611533 |
5,000 |
6 (7w) |
110 |
2.79 |
0.406 |
10.31 |
125 |
186 |
|
635290 |
|
4 (7w) |
110 |
2.79 |
0.452 |
11.48 |
180 |
268 |
Electrical Properties
|
Part Number |
Conductor |
Rdc (20˚C) |
Rac (90˚C, 60Hz) |
||
|
AWG |
ohm / km |
ohm / kft |
ohm / km |
ohm / kft |
|
|
660615 |
8 (19w) |
2.10 |
0.639 |
2.67 |
0.815 |
|
660616 |
6 (19w) |
1.32 |
0.402 |
1.68 |
0.513 |
|
611491 |
8 (7w) |
2.09 |
0.636 |
2.67 |
0.815 |
|
611533 |
6 (7w) |
1.31 |
0.400 |
1.67 |
0.510 |
|
635290 |
4 (7w) |
0.825 |
0.252 |
1.05 |
0.321 |
Physical Properties
|
Part Number |
Conductor |
Maximum Pulling |
Minimum Bend Radius |
Maximum Sidewall |
|||
|
AWG |
N |
lb |
mm |
in |
N / m |
lb / ft |
|
|
660615 |
8 (19w) |
577 |
130 |
47 |
1.9 |
1460 |
100 |
|
660616 |
6 (19w) |
917 |
206 |
52 |
2.0 |
1460 |
100 |
|
611491 |
8 (7w) |
577 |
130 |
48 |
1.9 |
1460 |
100 |
|
611533 |
6 (7w) |
917 |
206 |
52 |
2.0 |
1460 |
100 |
|
635290 |
4 (7w) |
1458 |
328 |
58 |
2.3 |
1460 |
100 |