Applications
ENERGEX® MC 120 cables may be used in standard commercial and industrial power, control, and lighting circuits. They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645. These cables may be installed in approved raceways and as open runs of cable on a messenger. They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300.22(C) with the jacket removed. The cables may also be installed in direct burial applications.
Nexans MC 120 wire is LEAD FREE and RoHS compliant.
Construction
Conductor:
Solid conductors and the wires for stranded conductors are soft annealed copper to ASTM B3.
Insulation:
PVC/Nylon type THHN in accordance to UL 83, flame resistant, meeting UL VW-1 flame test.
Ground Wire:
Bare copper, sized in accordance with NEC and UL, with green THHN insulation.
Assembly:
Conductors are cabled with grounding wires. A marker tape/core protection tape combination assembles the core in an essentially round configuration.
Armor:
Interlocking aluminum tape armor applied directly over the core.
Jacket: Black PVC jacket.
Marker Tape Print:
NEXANS TYPE MC 600 VOLT FOR CT USE (SIZE) THHN (UL) E-47409 LEAD FREE (MFG DATE)
Specifications
- Meets UL 83: Thermoplastic Insulated Wires and Cables
- Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to #2 AWG)
- Meets UL 1569: Metal Clad Cables
- Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords
- Meets UL 2556: Wire and Cable Test Methods
- Designated Type MC per NEC Article 330
|