ENERGEX® MC 120 Copper

Send link to this page print Your Nexans contact on this page
Aluminum Armored MC Cable UL Type MC, 600 Volts, 90ºC dry rated - LEAD FREE Copper conductors
Standards
National  UL 1569; UL 1581; UL 44; UL 83
Description

Application

ENERGEX® MC 120 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC Article 330.  They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645.  These cables may be installed in approved raceways and as open runs of cable on a messenger.  They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC Article 300.22(C) ONLY.

Nexans MC 120 wire is LEAD FREE and RoHS compliant.

  

Construction

Conductor
Solid conductors and the wires for stranded conductors are soft annealed copper to ASTM B3.

Insulation:
Colored PVC/Nylon type THHN in accordance with UL 83,  flame retardant, meeting UL VW-1 flame test for sizes #14 to #1 AWG. 
Colored cross-linked polyethylene type XHHW-2 per UL 44 for sizes 1/0 AWG and larger.

Ground Wire:
Bare copper, sized in accordance with NEC and UL, with green THHN insulation (green XHHW-2 for 1/0 and larger).

Assembly:
Conductors are cabled with grounding wires. A marker tape/core protection tape combination assembles the core in an essentially round configuration.

Armor:
Interlocking aluminum tape armor applied directly over the core.

 

Marker Tape Print

NEXANS TYPE MC 600 VOLT FOR CT USE (SIZE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

 

Specifications

  • Meets UL 44:  Thermoset Insulated Wires and Cables (#1/0 AWG and larger)
  • Meets UL 83: Thermoplastic Insulated Wires and Cables (#14 to #1 AWG)
  • Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to #2 AWG)
  • Meets UL 1569:  Metal Clad Cables
  • Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords
  • Designated Type MC per NEC Article 330

 TOP
Characteristics
Construction characteristics
Conductor material Copper  
Lead free Yes  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ENERGEX MC 120 Copper Conductor

Part Number

Number
of Con-
ductors

Conductor
Size
AWG

Ground
Size
AWG

Circuit Conductor
Colour Code

Nominal 
Diameter
Over Armor

Approximate 
Net
Cable Weight

Ampacity
amps

250 ft 
coil

1000 ft 
reel

inches

mm

lb/kft

kg/km

618777

642876

2

14 (1)

14 (1)

white/black

0.450

11.30

77

114

15

618785

642884

3

14 (1)

14 (1)

white/black/red

0.470

12.00

94

140

15

670050

670051

4

14 (1)

14 (1)

white/black/red/blue

0.510

12.80

112

167

15¹

618793

635045

2

12 (1)

12 (1)

white/black

0.480

12.30

104

155

20

618801

635052

3

12 (1)

12 (1)

white/black/red

0.510

13.10

130

194

20

618819

635060

4

12 (1)

12 (1)

white/black/red/blue

0.550

14.00

157

234

20¹

618827

636977

2

10 (1)

10 (1)

white/black

0.550

14.00

152

225

30

618835

636985

3

10 (1)

10 (1)

white/black/red

0.590

14.90

192

286

30

618843

640177

4

10 (1)

10 (1)

white/black/red/blue

0.640

16.30

234

348

30¹

642892

642900

2

12 (19)

12 (19)

white/black

0.480

12.30

107

159

20

644997

645002

3

12 (19)

12 (19)

white/black/red

0.510

13.10

134

200

20

645010

645028

4

12 (19)

12 (19)

white/black/red/blue

0.550

14.00

162

241

20¹

672972

672980

2

10 (19)

10 (19)

white/black

0.550

14.00

158

234

30

672576

672584

3

10 (19)

10 (19)

white/black/red

0.580

14.90

200

298

30

670017

672634

4

10 (19)

10 (19)

white/black/red/blue

0.640

16.30

243

362

30¹

200 ft reel

500 ft reel

 

670085

670190

2

8 (19)

10 (19)

white/black

0.660

16.70

213

317

55

670086

642918

3

8 (19)

10 (19)

white/black/red

0.710

18.10

280

416

55

670087

670208

4

8 (19)

10 (19)

white/black/red/blue

0.780

19.70

348

518

55¹

125 ft reel

500 ft reel

 

670088

670182

2

6 (19)

8 (19)

white/black

0.740

18.90

312

465

75

670089

643445

3

6 (19)

8 (19)

white/black/red

0.811

20.60

415

618

75

670090

670174

4

6 (19)

8 (19)

white/black/red/blue

0.890

22.50

519

772

75¹

680005

670539

3

4 (19)

8 (19)

white/black/red

0.940

23.90

599

891

95

---

673830

4

4 (19)

8 (19)

white/black/red/blue

1.060

26.80

857

1276

95¹

---

673848

3

3 (19)

6 (19)

white/black/red

1.020

25.80

840

1250

110

---

670237

4

3 (19)

6 (19)

white/black/red/blue

1.130

28.70

1054

1568

110¹

---

670521

3

2 (19)

6 (19)

white/black/red

1.090

27.70

986

1467

130

---

673871

4

2 (19)

6 (19)

white/black/red/blue

1.200

30.50

1251

1861

130¹

---

670184

3

1 (19)

6 (19)

white/black/red

1.200

30.60

1194

1777

150

---

670183

3

1/0 (19)

6 (19)

white/black/red

1.270

32.30

1338

1991

170

Bend Radius:    7 x overall diameter

Notes:

• Where stated, "nominal" and "approximate" values are provided for information purposes 
only and are subject to standard manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15, which are based
on NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or 
direct buried at 30°C ambient temperature.  Ampacities for cables having more than three 
conductors have been derated per NEC 2008 Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacities at different conduct 
temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
• NEC 2008 and NEC 2011 Article 240.4(D) required that over current protection not exceed 
15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper 
conductors after any correction factors for ambient temperature and number of conductors 
have been applied.  Exceptions to this may be covered in NEC 2008 and NEC 2011 
Article 240.4(E) through (G).

¹Where the 4th conductor is the neutral of a balanced 3 phase system. 



 TOP
Selling delivery information

Product Features

  • Cables are UL listed as Type MC, 600V
  • UL listed insulated conductors
  • Fire Wall Penetration rated depending on type of installation and fire-stop system used
  • UL listed for use in cable trays per NEC 330.10(A)
  • UL listed for use in Class I, Div. 2 per NEC 501.10(B)(6), Class II, Div.2 per NEC 502.10(B)(1) and Class III, Div. 1 & 2 per NEC 503.10(A) and (B) with approved termination fittings.
  • Temperature rating of 90ºC dry 
  • Excellent mechanical & physical properties
  • Lightweight aluminum armor
  • Conductor sizes larger than #1/0 AWG
  • LEAD FREE

 

Options

The following constructions can be provided on special orders:

  • Special conductor counts
  • XHHW-2 insulation on sizes #14 - #1 AWG
  • Conductor sizes larger than #1/0 AWG