ENERGEX® MC 277 Copper

Send link to this page print Your Nexans contact on this page
Aluminum Armored MC Cable with Special Color Codes for 277 Volt. UL Type MC, 600 Volts, 90ºC dry rated - LEAD FREE Copper conductors
Standards
National  UL 1569; UL 83
Description

Application

ENERGEX® MC 277 cables may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction in accordance with NEC 2008 and NEC 2011 Article 330.  They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC 2008 and NEC 2011 Articles 230.43, 300.22(C), 330, 396, 518, 520, 530 and 645.  These cables may be installed in approved raceways and as open runs of cable on a messenger.  They may be installed exposed, concealed or in cable tray and may be run in spaces used for environmental air in accordance with NEC 2008 and NEC 2011 Article 300.22(C) ONLY.

 

Nexans MC 277 wire is LEAD FREE and RoHS compliant.

   

Construction

Conductor
Solid soft bare, annealed copper per ASTM B3.  Stranded soft bare annealed copper per ASTM B3 and ASTM B787 for sizes 14 to 8 AWG and ASTM B8 for sizes 6 AWG and larger.

Insulation:
Colored PVC/Nylon type THHN per UL 83, flame retardant, meeting UL VW-1 flame test.

Ground Wire:
Bare copper, sized in accordance with NEC 2008 and NEC 2011 and UL, with green THHN insulation.

Assembly:
Conductors are cabled with grounding wires.  A marker tape/core protection tape combination assembles the core in an essentially round configuration.

Armor:
Interlocking aluminum tape armor applied directly over the core.

 

Marker Tape Print

NEXANS TYPE MC 600 VOLT FOR CT USE (SIZE) THHN (UL) E-47409 LEAD FREE (MFG DATE)

 

Specifications

  • Meets UL 83: Thermoplastic Insulated Wire and Cables
  • Tested to UL 1479: Fire Tests of Through-Penetration Firestops for one, two or three hour fire rated assemblies (for cables up to 2 AWG)
  • Meets UL 1569:  Metal Clad cables
  • Meets UL 1581: Reference Standard for Electrical Wire, Cable, and Flexible Cords
  • Designated Type MC per NEC 2008 and NEC 2011 Article 330

 


 TOP
Characteristics
Construction characteristics
Conductor material Copper  
Lead free Yes  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ENERGEX® MC 277 Volt Copper

Part Number

Number 
of Con-
ductors

Conductor
Size
AWG

Ground
Size
AWG

Circuit Conductor
Color Code

Nominal 
Diameter
Over Armor

Approximate 
Net
Cable Weight

Ampacity
amps

250 ft 
coil

1000 ft
 reel

inches

mm

lb/kft

kg/km

654269

652537

2

12 (1)

12 (1)

brown/gray

0.480

12.30

118

176

20

654251

671917

2

12 (1)

12 (1)

orange/gray

0.480

12.30

118

176

20

654244

671925

2

12 (1)

12 (1)

yellow/gray

0.480

12.30

118

176

20

672956

672964

2

12 (1)

12 (1)

purple/gray

0.480

12.30

118

176

20

676205

676213

2

12 (1)

12 (1)

brown/yellow

0.480

12.30

118

176

20

652263

670570

2

12 (1)

12 (1)

red/white

0.480

12.30

118

176

20

652271

670554

2

12 (1)

12 (1)

blue/white

0.480

12.30

118

176

20

669762

669770

3

12 (1)

12 (1)

brown/orange/gray

0.510

13.10

145

216

20

674937

674945

3

12 (1)

12 (1)

brown/purple/gray

0.510

13.10

145

216

20

674952

674960

3

12 (1)

12 (1)

purple/yellow/gray

0.510

13.10

145

216

20

674978

674986

3

12 (1)

12 (1)

brown/yellow/gray

0.510

13.10

145

216

20

675991

676006

3

12 (1)

12 (1)

red/blue/white

0.510

13.10

145

216

20

676015

676031

3

12 (1)

12 (1)

black/blue/white

0.510

13.10

145

216

20

671891

669812

4

12 (1)

12 (1)

brown/orange/yellow/gray

0.550

14.00

173

257

20¹

676049

676056

4

12 (1)

12 (1)

brown/purple/yellow/gray

0.550

14.00

173

257

20¹

672915

672923

2

10 (1)

10 (1)

brown/gray

0.550

14.00

164

244

30

672931

672949

3

10 (1)

10 (1)

brown/orange/gray

0.590

14.90

207

308

30

672592

672600

4

10 (1)

10 (1)

brown/orange/yellow/gray

0.640

16.30

244

363

30¹

---

---

2

12 (19)

12 (19)

brown/gray

0.480

12.30

118

176

20

---

---

3

12 (19)

12 (19)

brown/orange/gray

0.510

13.10

145

216

20

---

---

4

12 (19)

12 (19)

brown/orange/yellow/gray

0.550

14.00

173

257

20¹

---

---

2

10 (19)

10 (19)

brown/gray

0.550

14.00

164

244

30

---

---

3

10 (19)

10 (19)

brown/orange/gray

0.900

14.90

207

308

30

---

---

4

10 (19)

10 (19)

brown/orange/yellow/gray

0.640

16.30

244

363

30¹

500 ft reel

1000 ft reel

 

642918

----

3

8 (19)

10 (19)

brown/orange/gray

0.71

18.10

300

446

55

643445

---

3

6 (19)

8 (19)

brown/orange/gray

0.81

20.60

435

647

75

Bend Radius:    7 x overall diameter

Notes:
• Where stated, "nominal" and "approximate" values are provided for information purposes 
only and are subject to standard manufacturing tolerances.
• Ampacities are in accordance with NEC 2008 and NEC 2011 Article 310.15 and 334.80, which are based on NEC 2008 
Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C ambient 
temperature.  Ampacities for cables having more than three conductors have been derated per NEC 2008 
Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacities at different conduct temperature ratings see 
NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that over current protection not exceed 15 amperes for 14 AWG, 
20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after any correction factors for ambient 
temperature and number of conductors have been applied.  Exceptions to this may be covered in NEC 2008 and 
NEC 2011 Article 240.4(E) through (G).

¹Where the 4th conductor is the neutral of a balanced 3 phase system. 


 TOP
Selling delivery information

Product Features

  • Cables are UL listed as Type MC, 600V
  • UL listed insulated conductors
  • Fire Wall Penetration rated depending on type of installation and fire-stop system used
  • UL listed for use in cable trays per NEC 2008 and NEC 2011 Article 330.10(A)(6)
  • For use in Class I, Div. 2 per NEC 2009 and NEC 2011 Article 501.10(B)(1)(6), Class II, Div. 2 per NEC 2008 and NEC 2011 Article 502.10(B)(1)(6) and Class III, Div. 1 & 2 per NEC 2008 and NEC 2011 503.10(A) and (B) with approved termination fittings.
  • Temperature rating of 90ºC dry 
  • Excellent mechanical & physical properties
  • Lightweight aluminum armor
  • LEAD FREE

 