Instrumentation TC - 600 V - PVC Insulated, PVC Jacketed
See all Instrumentation TC - 600 V - PVC/Nylon Insulated products
Description
Standards
National : UL 1277Description
Applications
The 600 V Instrumentation Cables are listed as Type TC per UL 1277. These cables are suitable for installations as outlined in NEC 2008 and NEC 2011Article 336. These cables may be installed in wet or dry locations; in cable trays, raceways and pen air; and are suitable for exposure to weather, direct burial and for Class I, Div. 2 (also Zone 2) and Class II, Div. 2 hazardous locations per NEC 2008 and NEC 2011.
NEXANS Instrumentation Cable is LEAD FREE and RoHS Compliant.
Construction
Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance to ASTM B8.
Insulation: PVC/Nylon Type TFN in accordance with UL 66, flame retardant, 90°C temperature rating.
Insulation Shield (on shielded pair/triad constructions): Aluminum foil/polyester shield helically wrapped to provide 100% coverage with a tinned copper drain wire that is two gauge sizes smaller than the circuit conductors. These shields are electrically isolated from each other.
Assembly: Pairs/triads are cabled in concentric layers. In the case of unshielded pairs/triads, they are cabled at staggered lengths to reduce crosstalk.
Overall cable shield: Aluminum foil/polyester shield helically wrapped to provide 100% coverage with a tinned copper drain wire that is the same size as the circuit conductors, with the exception of single pair/triad constructions where the drain wire is two gauge sizes smaller than the circuit conductors.
Jacket: UL listed sunlight and moisture resistant, sequentially length marked, black, flame retardant polyvinyl chloride material. A Nylon ripcord is included for ease of jacket removal.
Conductor Identification
Pairs: black/white and number coded
Triads: black/white/red and number coded
Bending Radius
Fixed Position: 5 x cable overall diameter
During Installation: 8 x cable overall diameter
Specifications
- Meets UL 66: Fixture Wire for 18 AWG or 16 AWG, Type TFN rated 90°C 600 V conductors
- Meets UL 1277: Power and Control Tray Cables with Optional Fiber Members, requirements Type TC
- Designated Type TC per NEC 2008 and NEC 2011 Article 336
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Bare annealed copper |
| Outer sheath | PVC |
| Electrostatic shielding | Individual and Overall Shielded |
Docs and info
Instrumentation TC
|
600 V, PVC/Nylon Insulated, 90°C, |
||||||||||||
|
|
||||||||||||
|
Shielded Triads with an Overall Shield (STOS), 600 V |
||||||||||||
|
|
||||||||||||
|
Part |
# of |
Conductor |
Insulation |
Jacket |
Nominal Diameter |
Approximate Net |
Maximum |
|||||
|
AWG |
mils |
mm |
mils |
mm |
inches |
mm |
lb/kft |
kg/km |
lbf |
N |
||
|
689547 |
2 |
18 (7) |
15/4 |
.38/.10 |
47 |
1.19 |
0.453 |
11.51 |
117 |
170 |
68 |
303 |
|
631408 |
4 |
18 (7) |
15/4 |
.38/.10 |
62 |
1.57 |
0.557 |
14.15 |
190 |
283 |
149 |
664 |
|
631416 |
8 |
18 (7) |
15/4 |
.38/.10 |
62 |
1.57 |
0.718 |
18.24 |
327 |
487 |
303 |
1349 |
|
------ |
10 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
0.882 |
22.40 |
432 |
643 |
376 |
1674 |
|
697565 |
12 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
0.909 |
23.09 |
495 |
737 |
444 |
1977 |
|
------ |
16 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.008 |
25.60 |
628 |
935 |
599 |
2663 |
|
------ |
20 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.118 |
28.40 |
762 |
1134 |
753 |
3348 |
|
631424 |
24 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.242 |
31.55 |
899 |
1338 |
902 |
4012 |
|
631432 |
36 |
18 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.421 |
36.09 |
1279 |
1903 |
1351 |
6010 |
|
------ |
50 |
18 (7) |
15/4 |
.38/.10 |
112 |
2.84 |
1.734 |
44.04 |
1826 |
2717 |
1882 |
8370 |
|
|
||||||||||||
|
------ |
2 |
16 (7) |
15/4 |
.38/.10 |
47 |
1.19 |
0.509 |
12.93 |
156 |
232 |
108 |
483 |
|
631390 |
4 |
16 (7) |
15/4 |
.38/.10 |
62 |
1.57 |
0.624 |
15.85 |
253 |
377 |
238 |
1057 |
|
627133 |
8 |
16 (7) |
15/4 |
.38/.10 |
62 |
1.57 |
0.810 |
20.57 |
444 |
661 |
483 |
2148 |
|
------ |
10 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
0.993 |
25.22 |
581 |
865 |
599 |
2665 |
|
627141 |
12 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.024 |
26.01 |
671 |
999 |
708 |
3147 |
|
688648 |
16 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.138 |
28.91 |
858 |
1277 |
953 |
4238 |
|
------ |
20 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.265 |
32.13 |
1046 |
1557 |
1198 |
5329 |
|
683029 |
24 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.408 |
35.76 |
1238 |
1842 |
1436 |
6386 |
|
------ |
36 |
16 (7) |
15/4 |
.38/.10 |
82 |
2.08 |
1.615 |
41.02 |
1777 |
2644 |
2151 |
9568 |
|
------ |
50 |
16 (7) |
15/4 |
.38/.10 |
112 |
2.84 |
1.967 |
49.96 |
2523 |
3755 |
2995 |
13323 |
|
Note: Dimensions and weights shown are nominal values, subject to standard industry tolerances. |
||||||||||||
Related documents
Selling information
Options
The following constructions can be provided on special orders:
- Tinned copper conductors
- When increased mechanical, chemical, or environmental protection is required, cables can be supplied with a continuously welded and corrugated impervious aluminum sheath and an outer PVC jacket.
- Interlocked aluminum armor with or without an outer PVC jacket
- Conductors with alternate color / identification codes
- Alternate jacket colors
* Use in Hazardous locations:
Please note that no investigation of these cables has been performed regarding the transmission of gases or vapors through the core. When these cables are used in hazardous locations they should be sealed properly as required by the NEC.