Composite 12 Fiber OM2 with Two 18 AWG Stranded Conductors, Filled Loose Tube
|
|
|
|
|
Berk-Tek’s Composite Copper/Fiber cables incorporate high bandwidth optical fibers with insulated stranded copper TFFN or THWN conductors. A wide variety of design options are available including; up to 7 conductors ranging from #12 AWG to #18 AWG, up to 12 tight buffered fibers or 24 loose tube fibers, and interlock armoring. These cables are listed as CL3R-OF/PLTC-OF. A key application of these cables is to extend the distance that powered devices can be installed from the power source in Power over Ethernet (PoE+) installations. Proper conductor size selection can increase this distance from 328 feet to several thousand feet. The powered device could be an IP camera, a wireless access point, or other building automation device located in an area where an electrical outlet is not readily available.
|
|
|
|
|
Standards
|
|
International
|
EN 50173; ISO/IEC 11801
|
|
National
|
ANSI/ICEA S-104-696; ANSI/TIA-568-C.3; Telcordia GR-409; UL 13
|
|
Description
|
|
Construction
Each cable consists of multiple TFFN or THWN copper conductors and multiple fibers cabled together within an outer jacket. Cable design accommodates from 2 to 7 conductors and 2 to 24 fibers.
- Fibers can be tight buffered or in a loose tube
- Cable is dry-waterblocked for outdoor installations
- Aluminum (standard) or steel interlock armored cables available
Applications
Berk-Tek’s Composite cables are suitable for all power limited applications where optical fibers are needed. Specific applications include (but not limited to):
- Power over Ethernet (PoE+) length extension
- Combining control and communication in industrial pathways
- Common pathway for fiber backbone and Class 3 power supply
- 10BASE-FL
- 100BASE-SX/100BASE-FX
Features
- Multimode, Single-mode, and GIGAliteTM fibers
- CL3R-OF, wet and dry rated
- Aluminum or steel interlock armored designs available
- Indoor/Outdoor dry water-blocked designs available
Benefits
- Enables PoE+ equipment to be located more than 100 meters from the switch
- Cost savings versus installation of a new electrical outlet
- CL3R-OF/PLTC-OF allows cable to be installed in communication pathways
- Ease of installation
- Broad design selection allows for mix and match of copper and fiber components to specific networking applications
- Armor option adds crush resistance and protection from rodent attacks
|
|

 |
Related links
|
 |
|
TOP
|
Characteristics
|
|
Fiber optic type
|
OM2 50/125
|
|
|
Type of cable
|
Loose tube
|
|
|
Outer sheath
|
Fire-retardant PVC
|
|
|
Sheath colour
|
Black
|
|
|
Conductor material
|
Bare copper
|
|
|
Tube diameter
|
2.4mm
|
|
|
Number of optical fibres
|
12
|
|
|
Nominal outer diameter
|
0.35in
|
|
|
Nominal outer diameter
|
8.9mm
|
|
|
Approximate weight
|
76lb/kft
|
|
|
Approximate weight
|
51kg/km
|
|
|
Conductor cross-section (AWG)
|
18
|
|
|
Max. DC resistance of the conductor at 20°C
|
6.66Ohm/kft
|
|
|
Max. DC resistance of the conductor at 20°C
|
21.9Ohm/km
|
|
|
Optical performance
|
ZB (50/125 FDDI, OM2)
|
|
|
Attenuation, max. 850 nm (cabled)
|
3.5dB/km
|
|
|
Attenuation, max. 1300 nm (cabled)
|
1.5dB/km
|
|
|
Maximum installation tension
|
150lb
|
|
|
Maximum installation tension
|
668.0N
|
|
|
Max. Load. Long Term (lbs)
|
45.0lb
|
|
|
Max. Load. Long Term
|
200.0N
|
|
|
Impacts per TIA/EIA FOTP-25
|
2 at 5.88 N-m
|
|
|
Crush resistance per TIA/EIA FOTP-41
|
220N/cm
|
|
|
Cable flexibility per TIA/EIA FOTP-104
|
100 cycles
|
|
|
Minimum Bending Radius - Install
|
5.3in
|
|
|
Minimum Bend Radius - Install
|
13.4cm
|
|
|
Minimum Bending Radius - LongTerm
|
3.5in
|
|
|
Minimum Bending Radius - LongTerm
|
8.9cm
|
|
|
Operating temperature, range
|
-40 .. 75°C
|
|
|
Ambient installation temperature, range
|
-20 .. 60°C
|
|
|
Storage temperature, range
|
-60 .. 85°C
|
|
|
Field of application
|
Indoor, Outdoor
|
|
TOP
|
Fiber Type
|
ISO-TIA Standard
|
Effective Modal BW @ 850 nm
|
Overfilled Launch BW @ 850 nm
|
Attenuation @ 850 nm
|
Attenuation @ 1300 nm
|
Attenuation @ 1550 nm
|
Sheath Color
|
|
AB
|
OS2
|
NS
|
NS
|
NS
|
0.7 dB/km
|
0.7 dB/km
|
Black
|
|
CB
|
OM1
|
200 MHz-km
|
200 MHz-km
|
3.5 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
GB
|
OM1+
|
500 MHz-km
|
350 MHz-km
|
3.5 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
ZB
|
OM2
|
500 MHz-km
|
500 MHz-km
|
3.5 dB/km
|
1.5 dB/km
|
NS
|
Black
|
|
LB
|
OM2+
|
950 MHz-km
|
700 MHz-km
|
3.0 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
EB
|
OM3
|
2000 MHz-km
|
1500 MHz-km
|
3.0 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
FB
|
OM4
|
4700 MHz-km
|
3500 MHz-km
|
3.0 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
XB
|
OM4+
|
4900 MHz-km
|
3675 MHz-km
|
3.0 dB/km
|
1.0 dB/km
|
NS
|
Black
|
|
NS = Not Specified
|
TOP
|
Cross-sectional Diagram - OPRC6B012-002x18AWG
|
|

|
TOP
|
Manufacturing Release
|
|
IMPORTANT NOTICE: This product specification is provided for informational purposes only in order to illustrate typical product constructions, applications and/or methods of installation. Because conditions of actual installation and use are unique and will vary, Berk-Tek makes no representation or warranty as to the reliability, accuracy or completeness of this data, even if Berk-Tek is aware of the product's intended use or purpose. Furthermore, this data does not constitute, nor should it be regarded or relied upon, as professional engineering advice. Installation of cable should only be done by qualified personnel and in conformance with all safety, electrical and other applicable codes, standards, rules or regulations. Appropriate and correct product selection, installation and use, and compliance with all such codes, standards, rules and regulations, is a customer/end-user responsibility. Product specifications, standards, programs or services are subject to improvement or changes without notice. Berk-Tek accepts no liability for typographical errors, technical inaccuracies, omissions or misuse of the information contained herein. Changes will be periodically made to address any such issues.
|
TOP
|