Description
Nexans LANmark Industrial Medium-Duty Ethernet Cables enable the expansion and integration of Ethernet into the Industrial environment. With over 50 years of manufacturing expertise, you can be sure these Industrial Cables will perform both mechanically and electrically. With its 600V AWM design, PVC jacket, cold-bend performance, and resistance to oil, this cable is suitable for medium-duty, static, industrial applications. Additionally, the stranded conductors also help maintain performance in a high-vibration environment. It is rated CMR and CMX Outdoor, so it easily transitions from indoor to outdoor environments and is also suitable for cable tray installations.
Standards
International : ISO/IEC 11801; ODVA EtherNet/IP CompliantNational : ANSI/TIA-568-C.2; UL 444
Description
Construction
24 AWG stranded tinned copper wire insulated with HDPE. Two insulated conductors twisted together to form a pair and four such pairs to form the basic unit, enclosed by polyester tape, with PVC jacket.
Related Standards
Low Voltage - EU Directive 2014/35/EU, CE Approved
RoHS - EU Directive 2011/65/EU
PoE+ - Type 2 (802.3at)
ODVA EtherNet/IP™ Compliant
Ratings | ||
---|---|---|
Description | Method | |
Listed Type | UL1666 | CMR |
Listed Type | UL444 | CMX Outdoor |
Oil Resistance | UL1277 11.2 | I (60°C) |
Sunlight Resistance | UL444 7.12 | Yes (300 hrs) |
Attributes | ||
Description | Method | |
AWM Style | UL758 | 2463 (600V, 80°C) |
Cold Bend | UL444 7.10 | -40°C |
Installation Pull Tension (Max): | ||
Bend Radius: > 3 inch | Internal | 40 lbs. |
Bend Radius: > 1.00 inch | TIA 568-C.0 | 25 lbs. |
Abrasion | UL2556 7.10 | 75 cycles/1.5 lb. load |
Characteristics
Construction characteristics | |
---|---|
Conductor material | 24 AWG Stranded Tinned Copper (7/32) |
Insulation | HDPE |
Jacket Material | PVC |
Core Tape | Polyester |
Colour | Teal |
Dimensional characteristics | |
Insulated conductor diameter (Nominal) | 0.04in |
Average jacket thickness | 0.03in |
Minimum jacket thickness at any point | 0.024in |
Cable diameter (Nominal) | 0.25in |
Nominal cable weight | 34lb/kft |
Length per reel | 1000.0ft |
Electrical characteristics | |
Mutual capacitance | 5.6 nF/100m max. |
DC Resistance (max.) | 9.38Ohm/100m |
DC resistance unbalance (max.) | 5% |
Nominal velocity of propagation | 67% |
Maximum pair to ground unbalance | 330pF/100m |
Transmission characteristics | |
Skew (max.) | 45ns/100m |
Insertion loss de-rating factor | 1.2 |
Mechanical characteristics | |
Maximum installation tension | 25lb |
Usage characteristics | |
Packaging | Reel |
Minimum Bending Radius - Install | 1in |
Recommended installation temperature range | -20 .. 80°C |
Recommended operating temperature range | -40 .. 80°C |
Recommended storage temperature range | -40 .. 80°C |
Maximum cable length | 83m |
Docs and info
-
LANmark-B540 - Technical Information
Electrical Characteristics Parameter Frequency Equation RL (dB) 1-10 MHz 20+5*Log(F) 10-20 MHz 25 20-100 MHz 25-7*Log(F/20) Insertion Loss (dB/100m) 1-100 MHz (1.967*√F+0.023*F+0.050/√F)*1.2 NEXT (dB) 1-100 MHz 35.3-15*Log(F/100) PS-NEXT (dB) 1-100 MHz 32.3-15*Log(F/100) ACR (dB/100m) 1-100 MHz NEXT - Insertion Loss PS-ACR 1-100 MHz PS-NEXT - Insertion Loss ACRF (dB) 1-100 MHz 23.8-20*Log(F/100) PSACRF (dB) 1-100 MHz 20.8-20*Log(F/100) Propagation Delay 1-100 MHz 534+(36/√F) Transmission Characteristics Description ISO/IEC 11801 Category 5 ANSI/TIA-568-C.2 Category 5e ODVA EtherNet/IP™ Compliant Category 5e Color Code Pair-1 White/Blue Blue Pair-2 White/Orange Orange Pair-3 White/Green Green Pair-4 White/Brown Brown