4PR16(7)TYPEMC TFN HL 600VSPOS

Description

Description

Standards

  • National
    UL 1569; UL 2225; UL 66

Single or multiple individually shielded pairs or triads, overall cable shield, PVC inner
jacket, continuous corrugated aluminum sheath, PVC jacket

Construction

Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in
accordance with ASTM B8.


Insulation: PVC/Nylon type TFN in accordance with UL 66, flame retardant, 90°C
temperature rating.


Insulation shield: Aluminum foil/polyester shield helically wrapped to provide 100%
coverage and tinned copper drain wire that is two gauge sizes smaller than the circuit
conductors.


Assembly: Pairs/triads are cabled in concentric layers with interstices filled with
suitable non-hygroscopic fillers, as required. A binder tape of synthetic material
assembles the core in an essentially round configuration.


Overall cable shield: Aluminum foil/polyester shield helically wrapped to provide 100% coverage and tinned copper drain wire that is the same size as the circuit conductors.


Inner jacket: Polyvinyl chloride jacket, over cabled core as per UL 1569, 90°C temperature rating, with additional resistance to fire spread. A rip cord is laid longitudinally under the jacket to facilitate stripping.


Armor: Continuous corrugated aluminum sheath with no more than 0.2% trace copper providing complete protection against liquid & gas ingress. It also provides excellent mechanical protection, additional electrostatic shielding, and serves as an easy means of grounding equipment.


Jacket: Overall black polyvinyl chloride jacket per UL 1569, 90°C temperature rating;
low gas emission; limited flame spread and excellent corrosion resistance.


Identification of Conductors
Pairs: black/white & number coded
Triads: black/white/red & number coded


Bending Radius
Fixed position: 7 x cable overall diameter
During pulling: 12 x cable overall diameter


Specifications
* Meets UL 66, TFN rated 90°C 600 V conductors
* Meets UL 1569 requirements for Type MC, Metal Clad cables
* Meets UL 2225 for Hazardous Locations
* Designated Type MC as per NEC Article 330
* Marked “MC-HL” for installation and use in Class I Division 1 & 2, Class II Division 1 & 2, and Class III Hazardous Locations

 

Product Features

• UL approved cables Type MC, 600 V; File No. E47409
• UL approved insulated conductors
• Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000
BTU/hr, IEC 332-3 category A fire test, IEEE 1202 and CSA FT4
• Cables are American Bureau of Shipping (ABS) listed as CWC MC Type MC
• Cables exhibit a low temperature rating of -40ºC impact and –40ºC bend with suitable precautions
• Continuous, impervious aluminum sheath corrugated for flexibility, prevents ingress of moisture, gases and liquids
• Aluminum sheath resistance exceeds requirements of the NEC Article 250.178 for equipment grounding conductor
• Excellent mechanical and physical properties
• Minimal noise and signal interference
• Sunlight resistant jacket

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
EPR
Insulation colour
Black

Dimensional characteristics

Dimensional characteristics

Approximate net weight
440.22 kg/km
Cable Diameter
21.74 mm
Conductor Size (AWG)
16
Finished Cable Diameter
0.856 inches
Nominal cable weight
296 lb/kft
Number of strands
7

Electrical characteristics

Electrical characteristics

Maximum operating voltage
600 V

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close