CORFLEX® MC-HL / VFD

Description
Armored Power and Control Cable UL Type MC HL, 600 V, 90°C rated LEAD FREE
Description
Standards
National : UL 1569; UL 2225; UL 44Description
Multi-conductor 14 AWG to 10 AWG: Multiple conductors and composites, with ground
wire(s), continuous corrugated aluminum sheath, PVC jacket.
Construction
Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in
accordance with ASTM B8.
Insulation: Cross linked polyethylene type XHHW-2 per UL 44.
Assembly: Conductors are cabled in concentric layers with or without grounding wire
(s), interstices are filled with suitable non-hygroscopic fillers, as required. A binder tape
of synthetic material assembles the core in an essentially round configuration.
Armor: Continuous corrugated aluminum sheath with no more than 0.2% trace copper
providing complete protection against liquid & gas ingress. It also provides excellent
mechanical protection, additional electrostatic shielding, and serves as an easy means
of grounding equipment.
Jacket: Overall black polyvinyl chloride jacket per UL 1569, 90ºC temperature rating;
low gas emission; limited flame spread and excellent corrosion resistance.
Conductor Identification
Power and control:
Multi-conductor 14 AWG to 10 AWG: Method #1-E2 per ICEA S-73-532
3 conductor 8 AWG to 2 AWG: Method #1-E2 per ICEA S-73-532,
3 conductor 1 AWG to 500 kcmil: Method 4 per ICEA S-73-532
2 & 4 conductor 8 AWG to 750 kcmil: Method #4 per ICEA S-73-532
Composite power and control:
Power conductors: Method #4 per ICEA S-73-532
Control conductors: Method #1-E2 per ICEA S-73-532
Bending Radius
Fixed position: 7 x cable overall diameter
During pulling: 12 x cable overall diameter
Specifications
• Meets UL 44, XHHW-2 600 V conductors
• Meets UL 1569 requirements for Type MC, Metal Clad cables
• Meets UL 2225 for Hazardous Locations
• Designated Type MC as per NEC Article 330
• Meets CSA C22.2 No. 123-08 for Aluminum Sheathed Cables
• Meets CSA C22.2 No. 174-M1984 for Hazardous Locations
• Marked “MC-HL” for installation and use in Class I Division 1 & 2, Class II Division 1 & 2, and Class III Hazardous Locations
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Electrical characteristics | |
Maximum operating voltage | 600V |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
MULTICONDUCTORS, WITH BARE GOUND(S) ELECTRICAL DATA
Part |
# of |
Cond. |
|
AC |
Inductive |
Voltage |
Ampacities |
||
20ºC |
25ºC |
75ºC |
90ºC |
||||||
*12001844 |
3 |
14(7w) |
2.5553 |
1.0000 |
3.2583 |
0.0376 |
2.9489 |
15 |
15 |
*12000047 |
4 |
14(7w) |
2.5553 |
0.6488 |
3.2583 |
0.0376 |
2.9489 |
15 |
15 |
*12000056 |
5 |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0497 |
2.9542 |
15 |
15 |
*12000057 |
7 |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0545 |
2.9566 |
14 |
15 |
*12000058 |
9 |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0596 |
2.9585 |
14 |
15 |
*12000059 |
12 |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0641 |
2.9604 |
10 |
13 |
*12000060 |
19 |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0694 |
2.9627 |
10 |
13 |
|
|
|
|
|
|
|
|
|
|
*12001845 |
3 |
12(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0353 |
1.8610 |
20 |
20 |
*12000048 |
4 |
12(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0353 |
1.8610 |
20 |
20 |
*12000061 |
7 |
12(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0526 |
1.8685 |
18 |
20 |
*12000062 |
12 |
12(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0620 |
1.8726 |
13 |
15 |
|
|
|
|
|
|
|
|
|
|
*12001846 |
3 |
10(7w) |
1.0118 |
1.2902 |
1.2902 |
0.0332 |
1.1756 |
30 |
30 |
*12000049 |
4 |
10(7w) |
1.0118 |
1.2902 |
1.2902 |
0.0332 |
1.1756 |
28 |
30 |
* Stock Item |
|||||||||
Notes: |
MULTICONDUCTORS, WITH BARE GOUND(S) PHYSICAL DATA
Part Number |
# of |
Cond. |
Insulation |
Ground |
Nominal |
Nominal |
Jacket |
Nominal |
Approx. Net |
|
|
||||||||||
|
||||||||||
12001844 |
3 |
14(7w) |
30 |
3x18(7w) |
0.39 |
0.555 |
50 |
0.66 |
200 |
|
12000047 |
4 |
14(7w) |
30 |
14(7w) |
0.336 |
0.503 |
50 |
0.606 |
191 |
|
12000056 |
5 |
14(7w) |
30 |
14(7w) |
0.366 |
0.532 |
50 |
0.635 |
212 |
|
12000057 |
7 |
14(7w) |
30 |
14(7w) |
0.417 |
0.601 |
50 |
0.704 |
263 |
|
12000058 |
9 |
14(7w) |
30 |
14(7w) |
0.486 |
0.645 |
50 |
0.748 |
307 |
|
12000059 |
12 |
14(7w) |
30 |
14(7w) |
0.56 |
0.783 |
50 |
0.887 |
388 |
|
12000060 |
19 |
14(7w) |
30 |
14(7w) |
0.669 |
0.921 |
50 |
1.028 |
572 |
|
|
|
|
|
|
|
|
|
|
|
|
12001845 |
3 |
12(7w) |
30 |
3x16(7w) |
0.34 |
0.555 |
50 |
0.66 |
226 |
|
12000048 |
4 |
12(7w) |
30 |
12(7w) |
0.385 |
0.55 |
50 |
0.653 |
239 |
|
12000061 |
7 |
12(7w) |
30 |
12(7w) |
0.478 |
0.64 |
50 |
0.744 |
338 |
|
12000062 |
12 |
12(7w) |
30 |
12(7w) |
0.639 |
0.828 |
50 |
0.932 |
502 |
|
|
|
|
|
|
|
|
|
|
|
|
12001846 |
3 |
10(7w) |
30 |
3x14(7w) |
0.45 |
0.62 |
50 |
0.725 |
312 |
|
12000049 |
4 |
10(7w) |
30 |
10(7w) |
0.448 |
0.621 |
50 |
0.724 |
319 |
|
|
|
|
|
|
|
|
|
|
|
|
3 CONDUCTORS WITH 3 BARE GROUNDS* ELECTRICAL DATA
Part |
Cond. |
Ground |
DC |
AC |
Inductive |
Voltage |
Ampacities |
||
20ºC Ω/kft |
25ºC Ω/kft |
75ºC |
90ºC |
||||||
12001844 |
14(7w) |
3x18(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0376 |
2.9489 |
15 |
15 |
12001845 |
12(7w) |
3x16(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0353 |
1.8610 |
20 |
20 |
12001846 |
10(7w) |
3x14(7w) |
1.0118 |
1.0320 |
1.2902 |
0.0332 |
1.1756 |
30 |
30 |
*12001847 |
8(7w) |
3x14(7w) |
0.6361 |
0.6488 |
0.8111 |
0.0348 |
0.7452 |
50 |
55 |
*12001848 |
6(7w) |
3x12(7w) |
0.4002 |
0.4082 |
0.5104 |
0.0329 |
0.4737 |
65 |
75 |
*12001849 |
4(7w) |
3x12(7w) |
0.2516 |
0.2566 |
0.3209 |
0.0312 |
0.3024 |
85 |
95 |
*12001850 |
2(7w) |
3x10(7w) |
0.1574 |
0.1605 |
0.2009 |
0.0299 |
0.1938 |
115 |
130 |
*12001823 |
1/0(19w) |
3x10(7w) |
0.0999 |
0.1019 |
0.1278 |
0.0281 |
0.1272 |
150 |
170 |
*12001838 |
2/0(19w) |
3x10(7w) |
0.0797 |
0.0813 |
0.1021 |
0.0280 |
0.1041 |
175 |
195 |
*12001839 |
3/0(19w) |
3x8(7w) |
0.0629 |
0.0642 |
0.0808 |
0.0275 |
0.0847 |
200 |
225 |
*12001840 |
4/0(19w) |
3x8(7w) |
0.0497 |
0.0507 |
0.0641 |
0.0271 |
0.0695 |
230 |
260 |
*12001841 |
250(37w) |
3x8(7w) |
0.0424 |
0.0432 |
0.0584 |
0.0263 |
0.0608 |
255 |
290 |
*12001842 |
350(37w) |
3x6(7w) |
0.0301 |
0.0307 |
0.0395 |
0.0263 |
0.0470 |
310 |
350 |
*12001843 |
500(37w) |
3x6(7w) |
0.0212 |
0.0216 |
0.0290 |
0.0250 |
0.0367 |
380 |
430 |
*Stock Item |
|||||||||
Notes: |
3 CONDUCTORS WITH 3 BARE GROUNDS* PHYSICAL DATA
Part Number |
Cond. |
Insulation |
Ground |
Nominal |
Nominal |
Jacket |
Nominal |
Approx. Net |
|
|
|||||||||
|
|||||||||
12001844 |
14(7w) |
30 |
3x18(7w) |
0.390 |
0.555 |
50 |
0.660 |
200 |
|
12001845 |
12(7w) |
30 |
3x16(7w) |
0.340 |
0.555 |
50 |
0.660 |
226 |
|
12001846 |
10(7w) |
30 |
3x14(7w) |
0.450 |
0.620 |
50 |
0.725 |
312 |
|
*12001847 |
8(7w) |
45 |
3x14(7w) |
0.520 |
0.750 |
50 |
0.838 |
413 |
|
*12001848 |
6(7w) |
45 |
3x12(7w) |
0.600 |
0.802 |
50 |
0.905 |
542 |
|
*12001849 |
4(7w) |
45 |
3x12(7w) |
0.700 |
0.937 |
50 |
1.039 |
735 |
|
*12001850 |
2(7w) |
45 |
3x10(7w) |
0.830 |
1.127 |
50 |
1.232 |
1097 |
|
*12001823 |
1/0(19w) |
55 |
3x10(7w) |
1.040 |
1.350 |
50 |
1.473 |
1592 |
|
*12001838 |
2/0(19w) |
55 |
3x10(7w) |
1.126 |
1.422 |
50 |
1.510 |
1882 |
|
*12001839 |
3/0(19w) |
55 |
3x8(7w) |
1.250 |
1.606 |
60 |
1.739 |
2400 |
|
*12001840 |
4/0(19w) |
55 |
3x8(7w) |
1.360 |
1.734 |
60 |
1.867 |
2910 |
|
*12001841 |
250(37w) |
65 |
3x8(7w) |
1.477 |
1.925 |
60 |
2.058 |
3316 |
|
*12001842 |
350(37w) |
65 |
3x6(7w) |
1.685 |
2.028 |
60 |
2.162 |
4375 |
|
*12001843 |
500(37w) |
65 |
3x6(7w) |
1.954 |
2.340 |
75 |
2.504 |
6026 |
|
*Stock Item |
|
|
|
|
|
|
|
|
|
4 CONDUCTORS WITH 1 BARE GROUND ELECTRICAL DATA
Part |
Cond. |
Ground |
DC |
AC |
Inductive |
Voltage |
Ampacities |
||
20ºC |
25ºC |
75ºC |
90ºC |
||||||
12000047 |
14(7w) |
14(7w) |
2.5553 |
2.6064 |
3.2583 |
0.0375 |
2.9307 |
15 |
15 |
12000048 |
12(7w) |
12(7w) |
1.6082 |
1.6404 |
2.0506 |
0.0353 |
1.8510 |
20 |
20 |
12000049 |
10(7w) |
10(7w) |
1.0118 |
1.0320 |
1.2902 |
0.0332 |
1.1758 |
30 |
30 |
*12000050 |
8(7w) |
10(7w) |
0.6361 |
0.6488 |
0.8111 |
0.0348 |
0.7472 |
50 |
55 |
*12000051 |
6(7w) |
8(7w) |
0.4002 |
0.4082 |
0.5104 |
0.0329 |
0.4737 |
65 |
75 |
*12000052 |
2(7w) |
6(7w) |
0.1574 |
0.1605 |
0.2009 |
0.0299 |
0.1938 |
115 |
130 |
*12000053 |
2/0(19w) |
6(7w) |
0.0790 |
0.0806 |
0.1011 |
0.0281 |
0.1033 |
175 |
195 |
*12000054 |
4/0(19w) |
4(7w) |
0.0497 |
0.0507 |
0.0641 |
0.0271 |
0.0694 |
230 |
260 |
*12000055 |
500(37w) |
2(7w) |
0.0212 |
0.0216 |
0.0282 |
0.0250 |
0.0363 |
380 |
430 |
*Stock Item |
|||||||||
Notes: |
4 CONDUCTORS WITH 1 BARE GROUND PHYSICAL DATA
Part Number |
Cond. |
Insulation |
Ground |
Nominal |
Nominal |
Jacket |
Nominal |
Approx. Net |
|
|
|||||||||
|
|||||||||
12000047 |
14(7w) |
30 |
14(7w) |
0.336 |
0.503 |
50 |
0.606 |
191 |
|
12000048 |
12(7w) |
30 |
12(7w) |
0.396 |
0.549 |
50 |
0.652 |
245 |
|
12000049 |
10(7w) |
30 |
10(7w) |
0.450 |
0.620 |
50 |
0.730 |
320 |
|
*12000050 |
8(7w) |
45 |
10(7w) |
0.585 |
0.795 |
50 |
0.900 |
465 |
|
*12000051 |
6(7w) |
45 |
8(7w) |
0.680 |
0.930 |
50 |
1.027 |
675 |
|
*12000052 |
2(7w) |
45 |
6(7w) |
0.927 |
1.214 |
50 |
1.320 |
1332 |
|
*12000053 |
2/0(19w) |
55 |
6(7w) |
1.041 |
1.361 |
50 |
1.466 |
1628 |
|
*12000054 |
4/0(19w) |
55 |
4(7w) |
1.134 |
1.427 |
50 |
1.525 |
1922 |
|
*12000055 |
500(37w) |
55 |
2(7w) |
1.356 |
1.730 |
60 |
1.865 |
2975 |
|
*Stock Item |
|
|
|
|
|
|
|
|
|
Related documents
Selling information
Product features
• UL approved cables Type MC, 600 V; File No. E47409
• UL approved insulated conductors
• Cables pass UL 1685 and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA
T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE 1202 and
CSA FT4
• Cables are American Bureau of Shipping (ABS) listed as CWC MC Type MC
• Cables exhibit a low temperature rating of -40ºC impact and –40ºC bend with
suitable precautions
• Temperature rating of 90ºC dry and wet
• 130ºC emergency rating & 250ºC short circuit rating
• Continuous, impervious metallic sheath corrugated for flexibility, prevents ingress of
moisture, gases and liquids
• Aluminum sheath cross-section exceeds requirements of the NEC Section 250.122
for grounding conductor
• Sheath provides good electronic shielding so that Corflex® can be used in certain
instrumentation applications when adequately grounded
• Excellent mechanical & physical properties
• Sunlight resistant jacket
• Suitable for direct burial and use in cable tray and embedment in concrete
• LEAD FREE