48 x OS2 Adventum Riser Single Armor


See all Indoor/Outdoor Riser Adventum® – Single Armor Double Jacket (LTRA) products
Description
Standards
International : EN 50173; ISO/IEC 11801National : ANSI/ICEA S-104-696; ANSI/ICEA S-83-596; ANSI/TIA-568.3-D; Telcordia GR-409
Description
Berk-Tek's loose tube cable design can be used in all typical campus and outdoor/indoor installations, and is available with standard multimode, single-mode and GIGAlite™ fibers. This design affords the installer the ability to place cable anywhere in a network, bypassing the traditional transition points required in most installations. Adventum Riser cable is available in 2 to 288 count fiber constructions. These cables are suitable for Tray installations in industrial environments, and have been thoroughly tested in accordance with Telcordia GR-409 Issue 2, ICEA-596 Edition 3, and ICEA-696 Edition 2 standards where applicable.
Buffer Tube Construction
DryGel blocked color coded loose tubes containing up to 12, 250 µm, individually colored fibers.
Outdoor Consideration
Berk-Tek recommends that loose tube cables be utilized in an outside plant installation environment. Loose tube cables are especially recommended if the interbuilding conduit system is likely to fill with water.
Applications
Berk-Tek recommends installation procedures per ANSI/TIA-758, Customer-owned Outside Plant Telecommunications Infrastructure Standard.
Berk-Tek's Adventum Loose Tube, Riser Rated Rated fiber optic cable is intended for all high speed data applications, including:
- ETHERNET: 10BASE – 400GBASE (10BASE, 100BASE, 1000BASE, 10GBASE, 40GBASE, 100GBASE, 400GBASE)
- Fibre Channel: 1G-FC – 128GFC (1, 2, 4, 8, 16, 32, 128 GFC)
- SONET: OC-1 – OC-768 (OC -1, 3, 12, 24, 48, 192, 768)
- SDH: STM-0 – STM-256 (STM-0, 1, 4, 16, 64, 256)
- OTN: OTU-1 – OTU4 (OTU1, 2, 2e, 2f, 3, 3e2, 4)
- CPRI: CPRI-1 – CPRI-9 (CPRI-1, 2, 3, 4, 5, 6, 7, 7a, 8, 9)
- PON (SMF; I/O ONLY): RFoG, APON, BPON, EPON, GPON, WDM-PON, NG-PON
Features
- Designed to support Gigabit Ethernet, Gigabit ATM, Fibre Channel and other high-speed applications
- High tensile strength, crush resistant and small diameter design.
- Riser rating enables installation to go directly from outside plant to riser shaft
- Cable Core and Buffer Tubes use DryGel water blocking system
- UV resistant outer jacket protects the cable in outside plant installations
- Corrugated steel armor provides crush and rodent resistance.
Benefits
- Compact, water blocked, riser rated, flexible loose tube design allows for installation in any outside plant or interior space.
- Designed for direct burial installations.
- No cleaning of gels required for installation, greatly reducing installation time and cost
- Transition points in network are not needed
Characteristics
Construction characteristics | |
---|---|
Fiber optic type | SM (G657.A1) |
Type of cable | Loose tube |
Jacket Material | PVC |
Sheath colour | Black |
Armour type | Corrugated steel |
Dimensional characteristics | |
Tube diameter | 3mm |
Number of optical fibres | 48 |
Cable diameter (Nominal) | 0.575in |
Nominal outer diameter | 14.6mm |
Nominal cable weight | 147lb/kft |
Approximate weight | 219kg/km |
Transmission characteristics | |
Optical performance | AB (Single-mode, OS2) |
Attenuation, max. 1310 nm (cabled) | 0.4dB/km |
Attenuation, max. 1550 nm (cabled) | 0.3dB/km |
Mechanical characteristics | |
Maximum installation tension | 300lb |
Maximum installation tension | 1335N |
Max. Load. Long Term (lbs) | 90.0lb |
Max. Load. Long Term | 400.0N |
Impacts per TIA/EIA FOTP-25 | 2 at 5.88 N-m |
Crush resistance per TIA/EIA FOTP-41 | 440N/cm |
Cable flexibility per TIA/EIA FOTP-104 | 25 cycles |
Usage characteristics | |
Minimum Bending Radius - Install | 11.5in |
Minimum Bend Radius - Install | 29.2cm |
Minimum Bending Radius - LongTerm | 8.6in |
Minimum Bending Radius - LongTerm | 21.9cm |
RoHS compliant | Yes |
Recommended operating temperature range | -40 .. 75°C |
Ambient installation temperature, range | -20 .. 60°C |
Recommended storage temperature range | -60 .. 85°C |
Field of application | Indoor, Outdoor |
Docs and info
Standard Sheath Colors
Fiber |
Core |
ISO-TIA |
Effective Modal |
Overfilled Launch |
Attenuation |
Attenuation |
Attenuation |
Sheath Color |
AB |
8.3 |
OS2 |
NS |
NS |
NS |
0.4 dB/km |
0.3 dB/km |
Black |
CB |
62.5 |
OM1 |
200 MHz-km |
200 MHz-km |
3.5 dB/km |
1.0 dB/km |
NS |
Black |
EB |
50 |
OM3 |
2000 MHz-km |
1500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
FB |
50 |
OM4 |
4700 MHz-km |
3500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
XB |
50 |
OM4+ |
4900 MHz-km |
3675 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
NS = Not Specified |
-
Manufacturing Release
IMPORTANT NOTICE: This product specification is provided for informational purposes only in order to illustrate typical product constructions, applications and/or methods of installation. Because conditions of actual installation and use are unique and will vary, Berk-Tek makes no representation or warranty as to the reliability, accuracy or completeness of this data, even if Berk-Tek is aware of the product's intended use or purpose. Furthermore, this data does not constitute, nor should it be regarded or relied upon, as professional engineering advice. Installation of product should only be done by qualified personnel and in conformance with all safety, electrical and other applicable codes, standards, rules or regulations. Appropriate and correct product selection, installation and use, and compliance with all such codes, standards, rules and regulations, is a customer/end-user responsibility. Product specifications, standards, programs or services are subject to improvement or changes without notice. Berk-Tek accepts no liability for typographical errors, technical inaccuracies, omissions or misuse of the information contained herein. Changes will be periodically made to address any such issues.