500(37)AL 280TR 16X12CN LWBPEJ

Description

Description

Standards

  • International
    AEIC CS 8
  • National
    ICEA S-94-649

Description

 

Energex® CN Distribution Cables are suitable for use above ground in open air, in
cable tray, in conduit in air, aerially when suspended on a messenger wire, and
either directly buried or in duct. Energex® CN cables are suitable for continuous
operation from 90°C to 105°C, wet or dry, and are sunlight resistant.  

 


(Note: While suitable for use in cable tray, Energex® CN cables are not CT rated
as per UL 1072.)


There are a variety of features that can be chosen to further enhance the superior
quality inherent in these cables. These include an optional sealant for stranded
conductors, waterblocking components for the metallic shield, or high
performance conductor shield.

 

Construction Designs

The standard design consists of:

 

  • Voltage Rating from 5 kV to 46 kV using TR-XLPE
  • Copper Size Range from #8 to 1000 mcm
  • Aluminum Size Range from #2 to 1250 mcm
  • Conductor Strand block available in several configurations
  • Concentric Neutral sizing from 33% to 100% as required
  • Corrugated Copper Tapes available
  • Longitudinal water blocking between metallic shield and jacket available on request
  • Jackets available in PE or PVC or XLPE
  • Cable temperature rating from 90°C to 105°C


Standards
Nexans Energex® CN Distribution Cable is designed, manufactured, and tested
in accordance with the following standards and specifications:


AEIC CS8
Specification for Extruded Dielectric Shielded Power Cables Rated 5 Through 46 kV

 

ICEA S-97-682

Standard for Utility Shielded Power Cables 5 kV - 46 kV


ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5 kV - 46 kV


RUS Specification U-1
RUS Specification for 15 kV and 25 kV Primary Underground Power Cable

 

UL 1072

Standard for Medium-Voltage Power Cables (MV90 only)

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Insulation
XLPE
Insulation colour
-

Dimensional characteristics

Dimensional characteristics

Conductor Size (AWG)
500
Finished Cable Diameter
1.886 inches
Nominal cable weight
1590.551 lb/kft
Nominal outer diameter
- inches
Number of strands
37

Electrical characteristics

Electrical characteristics

Operating voltage - range
5 ... 46 kV

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close